Service
Securing the assets that cannot be patched on your schedule: industrial control systems, medical equipment, field devices and building infrastructure.
Factories, hospitals and utilities run equipment that cannot be switched off, cannot be updated on your schedule, and would break if you scanned it. We secure those environments by watching the network silently rather than touching the equipment, and by controlling what each machine is allowed to talk to.
Operational technology breaks every assumption IT security is built on. You cannot reboot it, you cannot patch it this quarter, and the vendor voids the warranty if you touch it. Security has to be designed around those constraints, not in spite of them.
| IT estate | OT / IoT estate | |
|---|---|---|
| Priority order | Confidentiality first | Availability and safety first |
| Patch cycle | Weeks | Years, in a scheduled outage window, if at all |
| Asset lifetime | 3–5 years | 15–25 years |
| Agent support | Assumed | Rare, and often contractually prohibited |
| Failure cost | Data loss | Physical consequence |
An agent-first vendor will quote you a rollout that cannot legally be installed on half your plant. The work is passive discovery, network-level enforcement and compensating control.
Mapping what is actually on the network by observing traffic, never by scanning. Active scanning has knocked over PLCs and infusion pumps in the field, and an unexpected probe on a safety system is an incident in its own right.
Detection built for Modbus, DNP3, BACnet, PROFINET and the proprietary protocols your vendors ship, so an anomalous setpoint change is visible as an anomalous setpoint change — not as unclassified TCP.
Where the device cannot be secured, the network around it is. Cell-level segmentation, strict conduits between zones, and enforcement in the switch and router rather than on an endpoint that cannot host software.
A documented, defensible position for every device that cannot be remediated — what the risk is, what control offsets it, and what evidence supports that for an auditor.
Discovery on an OT network is passive without exception. An active scan has knocked over PLCs, infusion pumps and building controllers in documented field incidents. Our capture interfaces are receive-only at the physical layer — an optical TAP with no transmit fiber, or a SPAN port on a switch where the sensor's NIC has its transmit pair physically unconnected. Configuration can be changed by mistake; a missing transmitter cannot.
| Protocol | Typical environment | What we decode | Built-in security |
|---|---|---|---|
| Modbus TCP | Manufacturing, water | Function codes, register writes, coil forcing | None — no authentication at all |
| DNP3 | Electric, water utilities | Object changes, control relay output, unsolicited responses | Optional (Secure Authentication v5), rarely enabled |
| BACnet | Building management | Property writes, priority array manipulation | Minimal |
| PROFINET | Discrete manufacturing | Cyclic data, alarms, config changes | None in common profiles |
| EtherNet/IP (CIP) | Rockwell estates | Tag reads and writes, firmware upload | Minimal |
| IEC 61850 | Substations | GOOSE, MMS, sampled values | Optional, seldom deployed |
The pattern is uniform: these protocols assume a physically protected network. That assumption is why segmentation, not endpoint hardening, is the primary control in OT.
Starting position: SCADA supervisory network bridged to corporate at three sites for reporting convenience. No inventory. Engineering laptops moved physically between sites and plugged into both networks. One site still used a dial-up modem for out-of-hours vendor access.
Roughly 240 controllers cannot be patched, will not be replaced within the decade, and speak unauthenticated protocols. No product changes that. What changed is that they now sit behind enforced conduits, are monitored for any deviation from a tight baseline, and each has a documented compensating control and named risk owner. That is the achievable outcome, and any vendor promising more is describing a different plant than the one you operate.
Bring us the estate you actually have — mixed OS fleets, ageing routers, unmanaged IoT — and we will tell you what can be unified under one agent and what needs custom work.